To answer the question, we first need to be clear about what each gas is, how it behaves, and what the purpose of a carbon monoxide (CO) detector is.
What is Carbon Monoxide?
- Carbon monoxide (CO) is a colorless, odorless, and tasteless gas that is produced by incomplete combustion of carbon-containing fuels (gas, wood, coal, petrol, etc.).
- Because CO binds strongly to hemoglobin in the blood, preventing oxygen transport, it is very dangerous even at moderate concentrations.
- A carbon monoxide detector (or CO alarm) is a device designed to sense elevated levels of CO in the air over time, and alert occupants before concentrations reach levels that pose serious health risk.
What is Natural Gas?
- “Natural gas” refers primarily to methane (CH₄) and associated hydrocarbons (e.g. ethane, propane) used as fuel.
- When untreated, natural gas is odorless, but odorants (e.g., mercaptans) are usually added so that leaks can be detected by smell.
- Natural gas is flammable and can form explosive mixtures with air.
- A gas leak (of natural gas) is dangerous principally because of explosion/fires and (in some settings) asphyxiation if it displaces oxygen.
Why the Question Arises?
Many people use gas for stoves, heaters, boilers, etc. They often already have CO detectors in their homes, so it’s reasonable to wonder whether those existing detectors protect against gas leaks too.
However:
- CO detectors are designed to detect carbon monoxide, not combustible gases.
- Natural gas is a different chemical species (primarily methane), which behaves differently, with different detection requirements.
- So one must examine whether a CO detector is sensitive to CH₄ (or other gas) and whether the design of CO detectors supports that.
The short answer is: No, a typical CO detector will not reliably detect a natural gas leak. But there are devices that combine both functions (gas + CO). Below we explore why the separation exists, how detection works, and what to use in practice.
Why CO Detectors Don’t Detect Natural Gas
1. Different Chemical Properties & Detection Principles
- CO detectors are built to sense CO molecules (or changes in air composition that correspond to CO). They are not optimized (or often even sensitive) to methane or other hydrocarbon gases.
- The sensors used in CO detectors (e.g. electrochemical, semiconductor, biomimetic) respond to CO (or oxidation of CO) in a controlled way. These sensors are not designed to respond to methane or other combustible gas leaks.
- The reaction kinetics, the sensor membranes, filters, calibration, and alarm thresholds are specific to CO, not to combustible gas detection.
2. Explosive Gas / Combustible Gas Detectors Use Different Technology
- Combustible gas detectors (for methane, propane, etc.) often use sensors that respond to flammability/hydrocarbon concentration, or changes in heat, catalytic combustion, infrared absorption, or catalytic bead sensors. These are sometimes called “explosive gas detectors.”
- These devices may measure the concentration relative to the Lower Explosive Limit (LEL) — i.e. the minimum concentration at which the gas will ignite.
- Because of this, a detector optimized for combustible gas must be designed differently, and its thresholds/response are different from those for CO.
3. Risk of False Readings
- If a detector attempted to detect both CO and methane using a CO sensor alone, it might either miss methane or give false alarms because the sensor is not selective.
- A CO detector is likely to ignore low levels of methane (because that is not its target gas) and may not alert until extremely high (and thus dangerous) methane levels (if at all).
Thus, a standalone CO detector is not a substitute for a gas (methane) detector.
Combined CO + Gas (Methane) Detectors
Because people often want protection from both carbon monoxide and natural gas leaks, the market offers combination detectors (CO + combustible gas). These devices include separate sensors or multimodal sensors to handle both types. Examples:
- First Alert GCO1CN: a combination “explosive gas + carbon monoxide” alarm that can sense methane and propane and alert to both threats.
- Universal Security Instruments MCND400B: a “plug-in 2-in-1 carbon monoxide and natural gas alarm.”
- DeNova Detect 10-year Battery CO + Natural Gas Alarm: uses MEMS sensor technology to detect natural gas leaks (10 % LEL threshold) and CO simultaneously.
- Some gas detectors also include CO functionality (or vice versa).
These combination devices typically have separate sensing elements or combined sensor modules designed to detect both CO and hydrocarbon gases. They are often certified to multiple standards (e.g., UL 2034 for CO, UL 1484 for combustible gas) in the US.
Hence, if you want to detect both, get a detector explicitly built for both, not rely on a CO-only device.
Standards, Certifications, and Alarm Thresholds
Understanding detector standards helps understand the limitations.
CO Detector Standards
- In the U.S., many CO alarms conform to UL 2034, which governs performance, testing, and alarm thresholds.
- Typical alarm thresholds: e.g. 70 parts per million (ppm) sustained over certain minutes, or higher levels in shorter time – detectors are designed so as not to alarm on minor transient CO.
- Lifespan: CO detectors’ sensors degrade over time; many have a 5–10 year service life.
Combustible Gas Detector Standards
- Devices that detect flammable gas (methane, propane, etc.) are often designed to trigger an alarm at some fraction of the LEL, e.g. 10 % LEL or 25 % LEL.
- They may follow UL 1484 (for combustible gas detectors) in the U.S. or equivalent regional standards.
- Because combustible gas detectors deal with explosion risk, their thresholds and response times are chosen with different criteria than CO detectors.
When devices combine CO + gas detection, they may need to conform to multiple standards or dual certifications.
Practical Considerations & Best Practices
When planning or assessing detectors in a home or facility, keep in mind the following:
Placement of Detectors
- CO detectors: generally placed at “breathing height” (knee to head height), often near bedrooms or rooms with fuel-burning appliances. CO is roughly the same density as air, so it doesn’t strongly rise or sink.
- Natural gas detectors: since methane is lighter than air, leaks tend to accumulate upward. So combustible gas detectors for natural gas are often mounted high (near ceiling). In contrast, if detecting propane (heavier than air), detectors go lower.
- Avoid interference: Don’t place detectors right next to gas appliances (to reduce nuisance alarms), drafts, windows, vents, or high-heat zones where readings might be skewed.
Maintenance and Testing
- Regularly test detectors (usually weekly or monthly) using the test button. But note: test buttons often check battery/electronics, not actual gas/CO sensing.
- Replace detectors when they reach “end of life” (EOL) as indicated by the manufacturer (often 7–10 years).
- Keep detectors clean — dust, debris, or paint may interfere with sensors.
Complementary Safety Measures
- Use separate gas leak detectors (or combined ones) in rooms with gas appliances (kitchen, boiler room).
- Ensure good ventilation, proper installation and maintenance of gas appliances, flues, and exhaust systems to avoid leaks and incomplete combustion (which produces CO).
- Install detectors near each sleeping area and on every floor.
- Educate occupants about the smell of gas (remembering that odorants might be missed) and to respond immediately to any alarm.
- In case of gas alarm: shut off supply (if safe), evacuate, ventilate, and call professionals.
Summary & Answer to the Question
- A carbon monoxide detector by itself does not reliably detect a natural gas leak, because CO and natural gas are different gases requiring different sensing mechanisms.
- CO alarms are tuned to detect carbon monoxide at concentrations relevant to human health — they are not sensitive (or selective) to methane or hydrocarbon gases.
- If you want protection against both CO poisoning and natural gas leaks, choose a dual-function or combination detector (CO + combustible gas), which includes specialized sensors for both.
- Always follow guidelines for installation, placement, maintenance, and replacement to ensure your detectors work when they’re needed.